Ratio Conversion Function; Output Setting Errors - Omron CS1W-AD041-V1 Operation Manual

Sysmac cs/cj series
Table of Contents

Advertisement

Ratio Conversion Function

6-7-3

Output Setting Errors

6-8

Ratio Conversion Function

262
To specify the output hold function, use a Programming Device to set the DM
Area words D(m+2) to D(m+5) as shown in the following table.
DM word
D(m+2)
Output 1: Output status when stopped
D(m+3)
Output 2: Output status when stopped
D(m+4)
Output 3: Output status when stopped
D(m+5)
Output 4: Output status when stopped
For the DM word addresses, m = D20000 + (unit number x 100).
Note After specifying the DM settings from a Programming Device, it will be neces-
sary to either turn the power to the PLC OFF and ON, or turn ON the Special
I/O Unit Restart Bit to transfer the contents of the DM settings to the Special I/
O Unit.
If the analog output set value is greater than the specified range, a setting
error signal will be stored in CIO word n+9 (bits 00 to 03).
Bit
15 14
Word n+9
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
The voltage for an output number at which a setting error has occurred will be
output according to the output hold function.
The Analog I/O Unit has a ratio conversion function that enables it to perform
analog-to-analog conversions by itself, without utilizing the PLC. It can use
either Loop 1 (input number 1 → output number 1), Loop 2 (input number 2 →
output number 2), Loop 3 (input number 3 → output number 3), or Loop 4
(input number 4 → output number 4).
Input 1 → Ratio bias calculation → Output 1
Input 2 → Ratio bias calculation → Output 2
Input 3 → Ratio bias calculation → Output 3
Input 4 → Ratio bias calculation → Output 4
Function
13
12
11
10
09 08
Section 6-8
Set value
xx00: CLR
Output 0 or mini-
mum value of range
(–5%).
xx01: HOLD
Hold output value
prior to stop.
xx02: MAX
Output maximum
value of range
(105%).
Set any value in the leftmost
bytes (xx).
07
06
05
04
03
02
When a setting error is detected
for a particular output, the corre-
sponding bit turns ON. When the
error is cleared, the bit turns OFF.
01 00