Indicators - Omron CS1W-AD041-V1 Operation Manual

Sysmac cs/cj series
Table of Contents

Advertisement

Components and Switch Settings
CS1W-AD161
34.5
130
Input connector 2
(Inputs 9 to 16)
2-3-1

Indicators

28
The terminal block is attached by a connector. It can be removed by loosening
the two black mounting screws located at the top and bottom of the terminal
block.
Check to be sure that the black terminal block mounting screw is securely
tightened to a torque of 0.5 N·m.
118.03
100.5
Input connector 1
(Inputs 1 to 8)
The indicators show the operating status of the Unit. The following table
shows the meanings of the indicators.
LED
Meaning
RUN (green) Operating
ERC (red)
Error
detected by
Unit
Fasten the mounting screw.
Fasten the mounting screw.
Backplane mounting screw
Indicator
Operating status
Lit
Operating in normal mode.
Not lit
Unit has stopped exchanging data with
the CPU Unit.
Lit
Alarm has occurred (such as disconnec-
tion detection) or initial settings are incor-
rect.
Not lit
Operating normally.
Section 2-3
Mode Switch
(two poles)
PC21 bus connector