Step Control Of Outdoor Unit Fans; Outdoor Unit Fan Control In Cooling Operation - Daikin RXYQ96PYDN Service Manual

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Basic Control
function is used to exert PI control on the electronic expansion valve (Y1E or Y3E) so that the
evaporator outlet superheated degree (SH) will become constant.
SH = Tg - Te
Subcooling electronic expansion valve EVT control
In order to make the maximum use of the subcool heat exchanger, this function is used to exert PI
control on the electronic expansion valve (Y2E, Y5E or Y3E) so that the evaporator-side gas pipe
superheated degree (SH) will become constant.
SH = Tsh - Te
Refrigerant charge electronic expansion valve EVJ control
While in automatic refrigerant charge mode, this function is used to exert PI control on the opening
degree of the electronic expansion valve (Y2E or Y4E) in response to outdoor temperature and
close the valve after the completion of refrigerant charge.
For normal operation, fully open this electronic expansion valve.
6.4

Step Control of Outdoor Unit Fans

Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes.
STEP No.
REYQ72P
0
0
1
285/255
2
315/285
3
360/330
4
430/400
5
590/560
6
690/660
7
820/790
8
920/890
9
920/890
Fan1/Fan2
* Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static
pressure or capacity precedence mode.
6.5

Outdoor Unit Fan Control in Cooling Operation

While in cooling operation, if the outdoor temperature is low, this mode provides high-pressure
control using the outdoor unit fan to retain appropriate liquid pressure, thus ensuring refrigerant
194
Single type
REYQ96P
REYQ120P
0
0
285/255
285/255
315/285
315/285
360/330
360/330
430/400
430/400
590/560
590/560
690/660
690/660
820/790
820/790
920/890
951/931
920/890
1020/990
Fan1/Fan2
Fan1/Fan2
SH : Evaporator outlet superheated degree (°F)
Tg : Suction pipe temperature (°F) detected by
the heat exchanger gas pipe thermistor
R2T.
Te : Low pressure equivalent saturated
temperature (°F)
SH: Evaporator outlet superheated degree (°F)
Tsh:Suction pipe temperature (°F) detected by
the subcool heat exchanger outlet
thermistor R5T
Te: Low pressure equivalent saturated
temperature (°F)
Fan revolutions (rpm)
REYQ144PTJU
REMQ72P
0
285/255
350
360/315
370
395/365
400
480/440
450
560/530
540
760/730
610
960/930
680
1155/1125
710
1200/1170
796
Fan1/Fan2
SiUS34-801A_b
Multiple type
REMQ96P
0
0
350
370
400
450
560
680
710
750
821
VRVIII R-410A Heat Recovery 60Hz
REMQ120P
0
350
370
400
450
560
680
710
775
870