Field Settings
a. Setting mode 1
This mode is used to set and check the following items.
Check items ··········· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Low noise operating conditions (In normal operation / In low noise operation)
(3) Demand operating conditions (In normal operation / In demand operation)
Procedure for checking check items
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, push the
MODE (BS1) button to set the
system to "Setting mode 1".
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Pushing the RETURN (BS3) button
will bring the system to the initial
state of "Setting mode 1".
100
MODE
TEST
H1P
H2P
7
7
(V2763)
COOL/HEAT select
Low
IND
MASTER
SLAVE
noise
H3P
H4P
H5P
H6P
8
7
7
7
Demand
H7P
7
Current operating conditions
7Normal 8Abnormal
9In preparation or in
check operation
Low noise operating conditions
7In normal operation
8In low noise operation
Demand operating conditions
7In normal operation
8In demand operation
VRVIII R-410A Heat Pump 60Hz
SiUS34-801A_b