Specifications
Heat Recovery 60Hz <REYQ-PTJU> 230V
Model Name
Power Supply
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor Output×Number
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Suction Gas Pipe
Pipes
High and Low Pressure
Gas Pipe
Mass
3 Sound Level (Reference Value)
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Standard Accessories
Drawing No.
Notes:
124
REYQ72PTJU
3 Phase 60Hz 208V-230V
Btu / h
72,000
Btu / h
81,000
Ivory White (5Y7.5/1)
66-1/8 × 51-3/16 × 30-1/8"
in (mm)
(1680 x 1300 x 765 mm)
Cross Fin Coil
Hermetically Sealed Scroll Type
3
m
/h
7.88+10.53
r.p.m
3720, 2900
kW
(2.4+7.0) × 1
Soft Start
Propeller Fan
kW
(0.35) × 2
cfm
6,700
Direct Drive
φ 3/8" (9.5 mm) C1220T
in (mm)
(Flare Connection)
φ3/4" (19.1 mm) C1220T
in (mm)
(Brazing Connection)
φ5/8" (15.8 mm) C1220T
in (mm)
(Brazing Connection)
Lbs (kg)
730 (331 kg)
dBA
High Pressure Switch,
Fan Driver Overload Protector,
Overcurrent Relay,
Inverter Overload Protector
Deicer
%
20~100
R-410A
Lbs
Electronic Expansion Valve
Installation Manual,
Operation Manual,
Connection Pipes, Clamps
4D058609
1 Indoor temp. : 80°FDB or 67°FWB / outdoor temp. : 95°FDB / Equivalent piping length :25 ft (7.5 m), level difference: 0 ft.
2 Indoor temp. : 70°FDB / outdoor temp. : 47°FDB or 43°FWB / Equivalent piping length :25 ft (7.5 m), level difference: 0 ft.
3 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
3 Phase 60Hz 208V-230V
Ivory White (5Y7.5/1)
66-1/8 × 51-3/16 × 30-1/8"
(1680 x 1300 x 765 mm)
Hermetically Sealed Scroll Type
φ 3/8" (9.5 mm) C1220T
(Flare Connection)
φ 7/8" (22.2 mm) C1220T
(Brazing Connection)
φ3/4" (19.1 mm) C1220T
(Brazing Connection)
58
High Pressure Switch,
Fan Driver Overload Protector,
Overcurrent Relay,
Inverter Overload Protector
22.7
Electronic Expansion Valve
Installation Manual,
Operation Manual,
Connection Pipes, Clamps
REYQ96PTJU
96,000
108,000
66-1/8 × 51-3/16 × 30-1/8"
Cross Fin Coil
Hermetically Sealed Scroll Type
13.34+10.53
6300, 2900
(4.2+7.0) × 1
Soft Start
Propeller Fan
(0.35) × 2
6,700
Direct Drive
730(331 kg)
58
Fan Driver Overload Protector,
Inverter Overload Protector
Deicer
14~100
R-410A
23.4
Electronic Expansion Valve
Connection Pipes, Clamps
4D058610
VRVIII R-410A Heat Recovery 60Hz
SiUS34-801A_b
REYQ120PTJU
3 Phase 60Hz 208V-230V
120,000
135,000
Ivory White (5Y7.5/1)
(1680 x 1300 x 765 mm)
Cross Fin Coil
13.34+10.53
6300, 2900
(6.0+6.8) × 1
Soft Start
Propeller Fan
(0.35) × 2
7,410
Direct Drive
φ1/2" (12.7 mm) C1220T
(Flare Connection)
φ1-1/8" (28.6 mm C1220T
(Brazing Connection)
φ3/4" (19.1 mm) C1220T
(Brazing Connection)
730(331 kg)
60
High Pressure Switch,
Overcurrent Relay,
Deicer
14~100
R-410A
23.8
Installation Manual,
Operation Manual,
4D058611