J2 Outdoor Unit: Current Sensor Malfunction - Daikin RXYQ96PYDN Service Manual

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
J2
3.25
Outdoor Unit: Current Sensor Malfunction
J2
Remote
Controller
Display
Applicable
RXYQ72P~240PYDN, PTJU
Models
REYQ72P~240PYDN, PTJU
Method of
Current value detected by current sensor.
Malfunction
Detection
Malfunction
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
Decision
standard compressor operation.
Conditions
Supposed
Causes
378
Faulty current sensor (A6P, A8P)
Faulty outdoor unit PC board
Defective compressor
SiUS34-801A_b