U0 Outdoor Unit: Gas Shortage Alert - Daikin RXYQ96PYDN Service Manual

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
U0
3.44
Outdoor Unit: Gas Shortage Alert
U0
Remote
Controller
Display
Applicable
RXYQ72P~240PYDN, PTJU
Models
REYQ72P~240PYDN, PTJU
Method of
Detect gas shortage based on the temperature difference between low pressure or suction pipe
Malfunction
and heat exchanger.
Detection
Malfunction
[In cooling mode]
Decision
Low pressure becomes 14.5psi or below.
[In heating mode]
Conditions
The degree of superheat of suction gas becomes 36 degrees and over.
SH= Ts1 –Te
Ts1: Suction pipe temperature detected by thermistor
Te : Saturated temperature corresponding to low pressure
Supposed
Causes
412
Malfunction is not determined. The unit continues operation.
Gas shortage or refrigerant clogging (piping error)
Defective thermistor (R4T, R7T, R12T, R15T)
Defective low pressure sensor
Defective outdoor unit PC board (A1P)