Step Control Of Outdoor Fans - Daikin Aurora Series Service Manual

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

Basic Control
5.6

Step Control of Outdoor Fans

Used to control the revolutions of outdoor fans in the steps listed in table below, according to condition changes.
Standard (default)
Step No.
Cooling
M1F
0
0
1
281
2
290
3
300
4
310
5
329
6
343
7
357
8
371
9
386
10
402
11
419
12
436
13
453
14
472
15
491
16
511
17
532
18
554
19
576
20
287
21
300
22
314
23
320
24
332
25
345
26
358
27
372
28
386
29
401
30
417
31
434
32
451
33
470
34
489
35
509
36
531
37
553
38
577
39
601
40
627
41
655
42
683
43
713
44
745
45
778
46
813
47
849
48
888
49
958
50
1040
51
1131
1021
52
1232
1132
53
1360
1180
53
Heating
M2F
M1F
M2F
0
0
0
0
281
0
0
290
0
0
300
0
0
310
0
0
329
0
0
343
0
0
357
0
0
371
0
0
386
0
0
402
0
0
419
0
0
436
0
0
453
0
0
472
0
0
491
0
0
511
0
0
532
0
0
554
0
0
576
0
317
287
317
330
300
330
344
314
344
350
320
350
362
332
362
375
345
375
388
358
388
402
372
402
416
386
416
431
401
431
447
417
447
464
434
464
481
451
481
500
470
500
519
489
519
539
509
539
561
531
561
583
553
583
607
577
607
631
601
631
657
627
657
685
655
685
713
683
713
743
713
743
775
745
775
808
778
808
843
813
843
879
849
879
918
888
918
928
958
928
930
1040
930
1131
1021
1232
1132
1360
1180
Step X
RXLQ72TA
RXLQ96TA
RXLQ120TA
RXYQ72TA
RXYQ96TA
RXYQ120TA
RXYQ144TA
RXYQ168TA
RXLQ72/96TA, RXYQ72TA cooling upper limit
RXLQ120TA, RXYQ96/120TA cooling upper limit
RXYQ144/168TA cooling,
All models heating upper limit
SiUS341802E
Cooling
Heating
49
51
51
51
52
52
49
51
51
52
52
52
53
53
53
53
Functions and Control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents