Daikin RXYQ96PYDN Service Manual page 480

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
[CHECK 8] Master Unit Central Connector Setting Table
The master unit central setting connector (CN1/X1A) is mounted at the factory.
(*1) The intelligent Touch controller and the schedule timer are not available for combined use.
(*2) The intelligent Touch controller, central remote controller, and the unified ON/OFF controller have been set to "Provided with the master
Troubleshooting
To independently use a single unit of the intelligent Touch controller or a single unit of the
central remote controller, do not dismount the master unit central setting connector (i.e., use the
connector with the factory setting unchanged).
To independently use the schedule timer, insert an independent-use setting connector.
No independent-use setting connector has been mounted at the factory. Insert the connector,
which is attached to the casing of the main unit, into the PC board (CN1/X1A).
(Independent-use connector=Master unit central setting connector)
To use two or more central equipment in combination, make settings according to the table
shown below.
Central equipment connection pattern
Central
Intelligent
Pattern
remote
Touch
controller
controller
1 to 2
units
1 unit
1 unit
1 to 2
units
1 to 4
units
unit central setting connector" at the factory. The schedule timer has been set to "Not provided with the master unit central setting
connector" at the factory, which is attached to the casing of the main unit.
Troubleshooting (OP: Unified ON/OFF Controller)
Setting of master unit central setting connector(*2)
Unified
Intelligent
Schedule
ON/OFF
Touch
timer
controller
controller
Only a
single unit:
× (*1)
"Provided",
Others: "Not
provided"
× (*1)
Provided
× (*1)
Only a
1 to 8
single unit:
units
× (*1)
"Provided",
Others: "Not
provided"
1 unit
1 to 16
units
1 unit
1 to 16
units
1 unit
1 unit
Central
Unified
remote
ON/OFF
controller
controller
Not provided
All "Not
provided"
Only a
single unit:
Not provided
All "Not
"Provided",
provided"
Others: "Not
provided"
Not provided
Only a
single unit:
"Provided",
Not provided
Others: "Not
provided"
Schedule
timer
Provided
465