Daikin RXYQ96PYDN Service Manual page 474

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
[CHECK
Check on connector of fan motor (Power supply cable)
(1) Turn off the power supply.
1]
[CHECK
(1) Turn off the power supply.
(2) While disconnected, measure the resistance between Vcc and each phase of U,V,W, and GND
2]
Troubleshooting
While disconnected, measure the resistance between phases U,V,W at the motor side
connectors (3-conductor wire) to check that the values are balanced and that there is no short
circuiting.
Red
White
Black
and each phase at the motor side connectors (five-core wire) to check that the values are
balanced within the range of ± 20 %.
To use a multiple meter for measurement, connect the probe of negative pole to Vcc and that of
positive pole to GND.
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
Troubleshooting (OP: Unified ON/OFF Controller)
U
Measure the resistance
V
values between phases
U,V,W.
W
GND
Vcc
Measure the resistance
values between Vcc
W
and U,V,W, and GND
and U,V,W.
V
U
459