Daikin RXYQ96PYDN Service Manual page 368

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
C5
3.10
Indoor Unit: Malfunction of Thermistor (R3T) for Gas
Pipes
C5
Remote
Controller
Display
Applicable
All indoor unit models
Models
Method of
.
Malfunction
Temperature of the gas pipe thermistor.
Detection
Malfunction
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Supposed
Causes
Troubleshooting
∗ Refer to the Thermistor Resistance / Temperature Characteristics table on Page 529.
Troubleshooting
Defect of indoor unit thermistor (R3T) for gas pipe
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Remove the thermistor from
the indoor unit PC board, and
then insert it again.
Is the
thermistor normal?
NO
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
5 kΩ to 90 kΩ
YES
Troubleshooting by Indication on the Remote Controller
YES
NO
Normal (The malfunction is
caused by faulty contact.)
Replace the thermistor (R3T).
Replace the indoor unit PC board.
353