Daikin RXYQ96PYDN Service Manual page 245

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Test Operation
3. Open the valve B (See the figure 30. The valve A,C and the liquid pipe, suction gas pipe, HP/
4. If the additional charging amount was charged fully, close the valve B and go to step 6.
5. Perform the refrigerant charging following [Automatic refrigerant charging operation
NOTE:
230
LP gas pipe, equalizer pipe shutoff valves must be left closed), and charge the refrigerant of the
additional charging amount from the liquid side shutout valve service port.
REYQ72~120PYDN
REYQ72~144PTJU
Measuring device
R-410A tank (with siphon)
REMQ72~120PYDN
REMQ72~120PTJU
Charge hose
Measuring device
R-410A tank (with siphon)
: Field pipings
: Refrigerant flow
If the additional charging amount was not charged fully, close the valve B and go to step 5.
procedure] as shown below. Charge the remaining refrigerant of the additional charging
amount.
For performing the automatic refrigerant charging operation, the push button on the PC-board
(A1) of outside unit is used. (See figure 29.)
The refrigerant is charged from the refrigerant charge port via the valve A. (See figure 31.) For
operating the push button and opening or closing the valves, follow the procedure.
During Automatic refrigerant charging operation, the system will select charging mode (cooling
mode or heating mode) by the temperature condition as follows.
Outdoor temp. : 32˚F DB ~ 109˚F DB
Indoor temp. :
Less than above range
When charging in cooling mode, the system will stop operation when the required amount of
refrigerant is charged.
During charging in heating mode, a person must manually close valve A and stop operation.
Beforehand, check the remaining refrigerant that is needed to charge based on the additional
charging amount in step 2 and the charged amount in step 3.
The refrigerant will be charged about 66 lb in one hour at outdoor temp. 86°F DB (about 26 lb at
outdoor temp. 32°F DB).
During Automatic refrigerant charging operation, you can stop the operation forcibly by pushing
Charge hose
Refrigerant charge port
Outside unit
HP/LP gas pipe shutoff valve
Suction gas shutoff valve
Liquid pipe shutoff valve
Valve B
Valve C
Valve A
: Field pipings
To BS,
: Refrigerant flow
indoor unit
Equalizer pipe shutoff valve
HP/LP gas pipe shutoff valve
Suction gas shutoff valve
Liquid pipe shutoff valve
Refrigerant charge port
Valve A
Valve B
Valve C
figure 30
50˚F DB ~ 90˚F DB
SiUS34-801A_b
: Shutoff valve
(
)
: Service port
Outside unit A
Outside unit B
: Shutoff valve
To BS,
(
:Service port
indoor unit
Cooling mode
Heating mode
VRVIII R-410A Heat Recovery 60Hz
)