SiUS34-801A_b
Image of operation in the case of A
Operation sound
Rated operation
sound
Operation sound of
Approx. 55 db (target)
level 1
Operation sound of
Approx. 50 db (target)
level 2
Operation sound of
level 3
Approx. 45 db (target)
Note1: Above values are reference only (measured in silent room)
Note2: Above values are for 1 module only.
Image of operation in the case of B
Operation sound
Time set with Nighttime Low Noise start setting.
Rated operation
sound
Operation sound
of level 1
Operation sound
of level 2
Operation sound
of level 3
Image of operation in the case of A and B
Time set with Nighttime Low Noise start setting.
Operation sound
of level 1
Operation sound
of level 2
Operation sound
Low noise mode commands
of level 3
operation sound with External
Low Noise setting.
VRVIII R-410A Heat Recovery 60Hz
If capacity precedence is set with the Capacity
Precedence setting, the fan speed increases
according to a heavier load of air conditioning.
If capacity precedence is set with the Capacity
Precedence setting, the fan speed increases
according to a heavier load of air conditioning.
Set with Nighttime Low Noise start setting.
(Factory setting is PM 10:00)
If capacity precedence is set with the Capacity
Precedence setting, the fan speed increases
according to a heavier load of air conditioning.
Operation noise can be
lowered by using the setting
External Low Noise Level.
(Factory setting is Mode 2)
Time set with NIGHTTIME LOW NOISE end setting
Operation sound during
low nighttime noise can be
set with NIGHTTIME LOW
NOISE LEVEL setting.
(Factory setting is OFF)
Set with Nighttime Low Noise setting.
(Factory setting is AM 8:00)
Time set with NIGHTTIME LOW NOISE end setting
Operation sound during low noise
mode can be set with the
External Low Noise Level setting.
(Factory setting is Mode 2)
Operation sound during
low nighttime noise can be
set with the Nighttime Low
Noise Level setting.
(Factory setting is OFF)
When external low noise Instruction is
commanded during Nighttime Low
Noise mode, Mode 2 precedes
Level 1, and Level 3 precedes Level 2.
Field Setting
257