Pump-Down Residual Operation - Daikin RXYQ96PYDN Service Manual

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
Evaporating outdoor unit actuator
Compressor 1
Compressor 2
Outdoor unit fan 1
Outdoor unit fan 2
Four way valve (for heat changer
selection)
Four way valve (for high- and low-
pressure gas pipe selection)
Electronic expansion valve (main)
Electronic expansion valve
(subcooling)
Electronic expansion valve
(refilling refrigerant)
Solenoid valve (main bypass)
Solenoid valve (hot gas)
Solenoid valve (liquid pipe of
refrigerant regulator)
Solenoid valve (gas discharge
pipe of refrigerant regulator)
Solenoid valve (drain pipe of
refrigerant regulator)
Solenoid valve (discharge pipe of
refrigerant regulator)
Cooling indoor unit actuator
Fan
Motorized valve
Heating indoor unit actuator
Fan
Motorized valve
Cooling BS unit actuator
Electronic expansion valve (EVH)
Electronic expansion valve (EVL)
Electronic expansion valve (EVHS)
Electronic expansion valve (EVLS)
Electronic expansion valve (EVSC)
Heating BS unit actuator
Electronic expansion valve (EVH)
Electronic expansion valve (EVL)
Electronic expansion valve (EVHS)
Electronic expansion valve (EVLS)
Electronic expansion valve (EVSC)
7.5

Pump-down Residual Operation

VRVIII R-410A Heat Recovery 60Hz
Elect. symbol
Symbol
REYQ REMQ
M1C
M1C REYQ72·96·120·144P: 232Hz+ON
REMQ72P: 210Hz
REMQ96·120P: 210Hz+ON
M2C
M2C
M1F
M1F
Fan control
M2F
M2F
Y2S
20SA
Y3S
ON
Y9S
20SB
Y8S
Y2S
Holds
Y1E
EVM
Y1E
PI control
Y3E
Y2E
EVT
Y3E
SH control
Y5E
EVJ
Y4E
Y2E
80pls
Y5S
SVE
Y6S
OFF
Y10S
SVP
Y4S
Y5S
OFF
SVL
Y3S
Y4S
0pls
SVG
Y1S
Y1S
0pls
SVO
Y7S
Y7S
0pls
SVT
Y6S
Y8S
0pls
Thermo ON unit
Unit not in operation
Thermo OFF unit
Thermo ON unit
Unit not in operation
Thermo OFF unit
Thermo ON unit
Unit not in operation
Thermo OFF unit
Thermo ON unit
Unit not in operation
Thermo OFF unit
Elect. symbol
Y4E
Y5E
Y2E
Y3E
Y1E
Elect. symbol
Y4E
Y5E
Y2E
Y3E
Y1E
Defrost operation
Defrost operation
Remote controller setting
Remote controller setting
Normal opening degree
Defrost operation
REYQ
LL
OFF
LL
160pls
0pls
160pls
Defrost operation
Defrost operation
0pls (REYQ72 · 96 · 120P) 60pls (REMQ72 · 96 · 120P)
0pls (PI control for cool/heat concurrent operation)
Special Control
Operation after defrost
REYQ72·96·120·144P: Upper limit
124Hz (STD Holds)
REMQ72P: 210Hz
REMQ96·120P: 210Hz+ON
Fan control
ON
Holds
PI control
0pls
80pls
OFF
OFF
0pls
0pls
0pls
0pls
OFF
0pls
0pls
REMQ
LL
OFF
LL
224pls
0pls
224pls
0pls
760pls
0pls
480pls
0pls
760pls
0pls
60pls
205