Daikin RXYQ96PYDN Service Manual page 201

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

Function General
Electric symbol
Symbol
REYQ72, 96, 120P
REYQ144PTJU
Ta
R1T (A1P)
R8T (Suction
pipe1)
TsA
R10T (Suction
pipe2)
R4T
(Deicer1)
Tb
R12T
(Deicer2)
R2T
(Gas pipe1)
Tg
R11T
(Gas pipe2)
R7T
(Liquid pipe1)
Tf
R15T
(Liquid pipe2)
R5T
(Gas pipe1)
Tsh
R13T
(Gas pipe2)
R6T
(Liquid pipe1)
Tl
R14T
(Liquid pipe2)
Tsc
R9T
Tc
TcS
Te
TeS
Tfin
R1T (A4P) (A5P)
Tp
Tdi
R31T (R32T) R31T
Tds
R32T
186
REMQ72, 96, 120P
R1T (A1P)
Outdoor air temperature
R8T
Suction pipe temperature
R4T
Heat exchanger outlet temperature at cooling
R2T
Heat exchanger gas pipe temperature
Temperature of liquid pipe between heat exchanger and main electronic expansion
R7T
valve
R5T
Temperature detected with the subcooling heat exchanger outlet thermistor
R6T
Liquid pipe temperature detected with the liquid pipe thermistor
R9T
Temperature of liquid pipe between liquid shutoff valve and subcooled heat exchanger
High pressure equivalent saturation temperature
Target temperature of Tc
Low pressure equivalent saturation temperature
Target temperature of Te
R1T (A3P)
Inverter fin temperature
Calculated value of compressor port temperature
Discharge pipe temperature of inverter compressor
R32T, R33T
Discharge pipe temperature of standard compressor
Description or function
VRVIII R-410A Heat Recovery 60Hz
SiUS34-801A_b

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents