Daikin RXYQ96PYDN Service Manual page 366

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
AJ
3.8
Indoor Unit: Malfunction of Capacity Determination
Device
AJ
Remote
controller display
Applicable
All indoor unit models
Models
Method of
Capacity is determined according to resistance of the capacity setting adaptor and the memory
Malfunction
inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal .
Detection
Malfunction
When the capacity code is not contained in the PC board's memory, and the capacity setting
Decision
adaptor is not connected.
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
The capacity setting adaptor was not installed.
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
The indoor
unit PC board was replaced
with a replacement
PC board.
YES
Was the
capacity setting
adapter mounted when
replacing the
PC board?
NO
Troubleshooting by Indication on the Remote Controller
NO
YES
Replace the indoor unit PC board.
Replace the indoor unit PC board.
Install a capacity setting adaptor.
(V2783)
351