Basic Control
5.6

Step Control of Outdoor Fans

Used to control the revolutions of outdoor fans in the steps listed in table below, according to condition changes.
Standard (default)
Step No.
Cooling
M1F
0
0
1
281
2
290
3
300
4
310
5
329
6
343
7
357
8
371
9
386
10
402
11
419
12
436
13
453
14
472
15
491
16
511
17
532
18
554
19
576
20
287
21
300
22
314
23
320
24
332
25
345
26
358
27
372
28
386
29
401
30
417
31
434
32
451
33
470
34
489
35
509
36
531
37
553
38
577
39
601
40
627
41
655
42
683
43
713
44
745
45
778
46
813
47
849
48
888
49
958
50
1040
51
1131
52
1232
53
1360
93
Heating
M2F
M1F
M2F
0
0
0
0
281
0
0
290
0
0
300
0
0
310
0
0
329
0
0
343
0
0
357
0
0
371
0
0
386
0
0
402
0
0
419
0
0
436
0
0
453
0
0
472
0
0
491
0
0
511
0
0
532
0
0
554
0
0
576
0
317
287
317
330
300
330
344
314
344
350
320
350
362
332
362
375
345
375
388
358
388
402
372
402
416
386
416
431
401
431
447
417
447
464
434
464
481
451
481
500
470
500
519
489
519
539
509
539
561
531
561
583
553
583
607
577
607
631
601
631
657
627
657
685
655
685
713
683
713
743
713
743
775
745
775
808
778
808
843
813
843
879
849
879
918
888
918
928
958
928
930
1040
930
1021
1131
1021
1132
1232
1132
1180
1360
1180
Step X
RXYQ72XA
RXYQ72XB
RXYQ96XA
RXYQ96XB
RXYQ120XA
RXYQ120XB
RXYQ144/168XA
RXYQ144/168XB
72 class cooling upper limit
96/120 class cooling upper limit
144/168 class cooling,
All models heating upper limit
SiUS342004EB
Cooling
Heating
49
51
51
52
52
52
53
53
Part 4 Functions and Control