Precautions for New Refrigerant (R-410A)
7. Precautions for New Refrigerant (R-410A)
1.1
Outline
1.1.1 About Refrigerant R-410A
1. Performance:
2. Pressure:
3. Refrigerant composition:
536
Characteristics of new refrigerant, R-410A
Almost the same performance as R-22 and R-407C
Working pressure is approx. 1.4 times more than R-22 and R-407C.
Good composition control, since it is a Quasi-azeotropic mixture refrigerant.
Refrigerant name
Non-azeotropic mixture of
Composing
HFC32, HFC125 and
substances
HFC134a (*1)
3.2 MPa (gauge pressure)
Design pressure
= 32.6 kgf/cm
= 464 psi
Refrigerant oil
Ozone destruction
factor (ODP)
Combustibility
Toxicity
1. Non-azeotropic mixture refrigerant: mixture of two or more refrigerants having different boiling
points.
2. Quasi-azeotropic mixture refrigerant: mixture of two or more refrigerants having similar boiling
points.
3. The design pressure is different at each product. Please refer to the installation manual for
each product.
(Reference) 1 MPa
10.19716 kgf / cm
1 MPa
145 psi
HFC units (Units using new refrigerants)
R-407C
Quasi-azeotropic mixture
of HFC32 and JFC125
(*1)
4.0 MPa (gauge pressure)
2
= 40.8 kgf/cm
= 580 psi
Synthetic oil (Ether)
0
None
None
2
Pressure-Enthalpy curves of HFC-32/125 (50/50wt%)
HCFC units
R-410A
Single-component
refrigerant
2.75MPa (gauge pressure)
2
= 28.0 kgf/cm
= 399 psi
Mineral oil (Suniso)
0
None
None
Precautions for New Refrigerant (R-410A)
SiUS34-801A_b
R-22
2
0.05
None
None