Basic Control
Two-unit multi system
REYQ144PYDN (6/6 ton)
(To increase Step No.)
STEP
unit 1
unit 2
No.
INV
INV
1
52Hz
52Hz
2
56Hz
56Hz
3
62Hz
62Hz
4
66Hz
66Hz
5
70Hz
70Hz
6
74Hz
74Hz
7
80Hz
80Hz
8
88Hz
88Hz
9
92Hz
92Hz
10
96Hz
96Hz
11
104Hz
104Hz
12
110Hz
110Hz
13
116Hz
116Hz
14
124Hz
124Hz
15
132Hz
132Hz
16
144Hz
144Hz
17
158Hz
158Hz
18
166Hz
166Hz
19
176Hz
176Hz
20
80Hz
80Hz
21
88Hz
88Hz
22
96Hz
96Hz
23
104Hz
104Hz
24
116Hz
116Hz
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master Unit and Slave Unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
192
(To decrease Step No.)
STEP
unit 1
unit 2
No.
INV
Initial step
1
52Hz
2
56Hz
3
62Hz
4
68Hz
5
74Hz
6
80Hz
7
88Hz
8
96Hz
9
104Hz
10
52Hz
52Hz
11
56Hz
56Hz
12
62Hz
62Hz
13
66Hz
66Hz
14
70Hz
70Hz
15
74Hz
74Hz
16
80Hz
80Hz
17
88Hz
88Hz
18
92Hz
92Hz
19
96Hz
96Hz
20
104Hz
104Hz
21
110Hz
110Hz
22
116Hz
116Hz
23
124Hz
124Hz
24
132Hz
132Hz
25
52Hz
52Hz
26
62Hz
62Hz
27
68Hz
68Hz
28
74Hz
74Hz
29
80Hz
80Hz
30
88Hz
88Hz
31
96Hz
96Hz
32
104Hz
104Hz
33
116Hz
116Hz
34
124Hz
124Hz
35
132Hz
132Hz
36
144Hz
144Hz
37
158Hz
158Hz
38
176Hz
176Hz
39
188Hz
188Hz
40
202Hz
202Hz
41
210Hz
210Hz
REYQ168PYDN, 192PYDN (6+8/10 ton)
(To increase Step No.)
STEP
unit 1
unit 2
INV
No.
INV
INV
1
52Hz
52Hz
2
56Hz
56Hz
3
62Hz
62Hz
4
66Hz
66Hz
5
70Hz
70Hz
6
74Hz
74Hz
7
80Hz
80Hz
8
88Hz
88Hz
9
92Hz
92Hz
10
96Hz
96Hz
11
104Hz
104Hz
12
110Hz
110Hz
13
116Hz
116Hz
14
124Hz
124Hz
15
132Hz
132Hz
16
144Hz
144Hz
17
158Hz
158Hz
18
166Hz
166Hz
19
176Hz
176Hz
20
80Hz
80Hz
21
88Hz
88Hz
22
96Hz
96Hz
23
104Hz
104Hz
24
116Hz
116Hz
(To decrease Step No.)
STEP
unit 1
unit 2
STD
No.
INV
INV
Initial step
1
52Hz
2
56Hz
3
62Hz
4
68Hz
5
74Hz
6
80Hz
7
88Hz
8
96Hz
9
104Hz
10
52Hz
52Hz
11
56Hz
56Hz
12
62Hz
62Hz
13
66Hz
66Hz
14
70Hz
70Hz
15
74Hz
74Hz
16
80Hz
80Hz
17
88Hz
88Hz
18
92Hz
92Hz
19
96Hz
96Hz
ON
20
104Hz
104Hz
ON
21
110Hz
110Hz
ON
22
116Hz
116Hz
ON
23
124Hz
124Hz
ON
24
132Hz
132Hz
25
52Hz
52Hz
26
62Hz
62Hz
27
68Hz
68Hz
28
74Hz
74Hz
29
80Hz
80Hz
30
88Hz
88Hz
31
96Hz
96Hz
32
104Hz
104Hz
33
116Hz
116Hz
34
124Hz
124Hz
35
132Hz
132Hz
36
144Hz
144Hz
37
158Hz
158Hz
38
176Hz
176Hz
39
188Hz
188Hz
40
202Hz
202Hz
41
210Hz
210Hz