Panasonic VF0 Series Instruction Manual page 87

Compact inverter 400v class
Hide thumbs Also See for VF0 Series:
Table of Contents

Advertisement

Enclosure
Cooling method
Downloaded from
www.Manualslib.com
Output specifications : 1c contact (contact capacity 250VAC, 0.5A
Relay output
Output functions
Output frequency or line speed (selection changeover), output current,
Operating condition
rotation direction
Symbol indicated when protective function activates (last 4 faults are
Fault details
stored).
Current limit
Current limit can be set from 1 to 200% of rated output current
Instantaneous overcurrent, over temperature (SC1 to 3), overcurrent
Shut-off (stop)
(OC1 to 3), overload/electronic thermal overload (OL), low voltage (LU),
overvoltage (OU1 to 3), auxiliary stop (AU), , operation error (OP)
Stall prevention
Overcurrent stall prevention, regenerative overvoltage stall prevention
function
Working ambient
–10°C to +50°C (with no freezing),
temperature and
90% RH or less (with no dew condensation)
humidity
Transportation/
storage temperature
–25°C to +65°C, 95% RH or less
and humidity
Altitude and
1000 m or less, 5.9 m/s
vibration
Indoors, with no corrosive gases, explosive gases, oil mist or dust
Atmosphere
present
IP00
Self-cooling
Forced-air cooling : 1.5 to 3.7kW
manuals search engine
resistance load)
: Run signal, arrival signal, overload prealarm,
frequency detection, reverse run signal, fault
warning,
2
(0.6G) or less