Panasonic VF0 Series Instruction Manual page 49

Compact inverter 400v class
Hide thumbs Also See for VF0 Series:
Table of Contents

Advertisement

OUTPUT TR FUNCTION SELECT (Parameter P25)
Used to set the functions of the open collector output (control terminals No. 10 -11).
Data setting
Note) The output frequency proportion or output current proportion for setting data "7" is
OUTPUT RY FUNCTION SELECT (Parameter P26)
Used to set the functions of the relay output (control terminals A, B and C).
Data setting
Downloaded from
www.Manualslib.com
Function
value
0
Run signal
1
Arrival signal
2
Overload prealarm
Frequency detection
3
signal
4
Reverse run signal
5
Fault warning signal (1) ON when the inverter is in the fault trip state
6
Fault warning signal (2)
7
Output status signal
set with parameter P58.
Function
value
0
Run signal
1
Arrival signal
2
Overload prealarm
Frequency detection
3
signal
4
Reverse run signal
5
Fault warning signal (1)
6
Fault warning signal (2)
manuals search engine
Conditions for open collector output to turn ON
(Setting data "7" is the PWM signal output)
ON when start input signal is ON or during inverter output
ON when the output frequency is within the set frequency
±2Hz
ON when the output current is 140% of the rated current or
higher or when the electronic thermal level is reached
ON when the output frequency exceeds the detected
frequency (set in parameter P27)
ON when the inverter is running in reverse
ON when the inverter is in the normal state (OFF when the
fault trip state is entered)
PWM signal proportional to the output frequency or output
current is constantly output
Conditions for relay to turn ON
(across terminals A-C: ON, across terminals B-C: OFF)
ON when start input signal is ON or during inverter output
ON when the output frequency is within the set frequency
±2Hz
ON when the output current is 140% of the rated current or
higher or when the electronic thermal level is reached
ON when the output frequency exceeds the detected
frequency (set in parameter P28)
ON when the inverter is running in reverse
ON when the inverter is in the fault trip state
ON when the inverter is in the normal state (OFF when the
fault trip state is entered)
48