Panasonic VF0 Series Instruction Manual page 50

Compact inverter 400v class
Hide thumbs Also See for VF0 Series:
Table of Contents

Advertisement

DETECT FREQUENCIES [OUTPUT TR], [OUTPUT RY]
Used to set the frequency to be detected when outputting the frequency detection signal
with the open collector output or relay output.
[Parameter P27 : Open collector output detection frequency setting]
[Parameter P28 : Relay output detection frequency setting]
Data setting range
Setting unit
♦ ♦ ♦ ♦ Relation of output frequency and each output signal
Output frequency
Run signal (OFF)
Frequency detection signal (OFF)
Arrival signal (OFF)
JOG FREQUENCY, JOG ACCELERATION TIME, JOG DECELERATION
TIME (Parameter P29, P30 and P31)
Used to set the operating frequency, acceleration/deceleration time when jog operation is
executed.
[Parameter P29: Jog frequency setting]
Data setting range
[Parameter P30 : Jog acceleration time setting]
[Parameter P31 : Jog deceleration time setting]
Data setting range
Note)
[Jog operation]
· The operation command select must be set to external control.
·
·
·
49
Downloaded from
www.Manualslib.com
(Hz) 000 • 0.5 to 250
(Hz) 0.1 (0.5 to 100Hz) 1 (100 to 250Hz)
(Hz) 0.5 to 250
(sec.) 0.04 • 0.1 to 999
"000" is displayed for 0.04 seconds.
(The data for parameter P08 must be set between "2 and 5".)
The SW select function must be set to the jog function.
If the SW set for the jog function turns ON (closed), the inverter will enter the jog
operation preparation completed state.
Carry out jog operation start/stop and forward/reverse with control terminals No. 5 and 6.
manuals search engine
(Parameter P27 and P28)
(ON)
(ON)
(OFF)
(ON)
(ON)
Set frequency (±2Hz)
Detection frequency
Parameter P27
Parameter P28
(OFF)
(OFF)
(OFF)