LOWER and UPPER FREQUENCY CLAMP
Used to set the lower and upper limits of the output frequency.
[Parameter P53 : Lower frequency clamp setting]
[Parameter P54 : Upper frequency clamp setting]
Data setting range
Setting unit
57
Downloaded from
www.Manualslib.com
(Hz) 0.5 to 250
(Hz) 0.1 (0.5 to 100Hz), 1 (100 to 250Hz)
Max. frequency (Parameter P15)
Upper frequency
clamp
(Parameter P54)
Lower frequency
clamp
(Parameter P53)
0
Set frequency signal
manuals search engine
Note 1) If the upper frequency clamp is lower
than the maximum output frequency
(parameter P15), the upper frequency
clamp will have the priority.
Note 2) If the lower frequency clamp is higher
than the upper frequency clamp, the
upper frequency clamp will have the
100%
priority.
(Parameter P53 and P54)