LOCAL/EXTERNAL CONTROL (Parameter P08)
Used to select whether to carry out start/stop and forward/reverse with the operation panel
(local) or with signals input from external devices.
Data
setting
value
0
1
2
4
3
5
∗ ∗ ∗ ∗ Panel reset function
When a fault trip occurs, the state cannot be reset with the external stop signal. Instead use
"function to reset with the stop SW signal on the operation panel". Note that if the reset lock
out function is used, that function will have the priority. The reset function is also valid.
LOCAL/EXTERNAL FREQUENCY (Parameter P09)
Used to select whether the frequency signal is to be set from the operation panel (local) or
with an input signal (external).
Data
setting
value
0
1
2
3
4
5
Note 1) When using the 4 to 20mA signal, always connect a "200Ω resistor" across
Note 2) When using an analog signal set to a value other than "1", the inverter will start
Downloaded from
www.Manualslib.com
Panel
Local/
Operation method and control terminal connection diagram
reset
External
function
Start: RUN Stop: STOP
Forward/reverse: Set in dr mode
Local
Provided
Forward run:
Not
3
provided
5
External
6
Provided
Not
3
provided
5
External
6
Provided
Local/
Frequency setting
signal details
External
Potentiometer (panel)
Local
Digital setting (panel)
Potentiometer
0–5(V) voltage signal
External
0–10(V) voltage signal
4–20(mA) current signal
terminals No. 2 and 3. (The inverter could be damaged if the 200Ω resistor is not
connected.)
and stop at a boundary of approx. 1/100 of the input signal's full scale. (0V stop
function: refer to page 73.)
manuals search engine
, RUN Stop: STOP
, RUN Reverse run:
Common terminal
ON: Start/OFF: Stop
ON: Reverse/OFF: Forward
Common terminal
ON: Forward run/OFF: Stop
ON: Reverse run/OFF: Stop
Operation method and control terminal
connection diagram
Frequency setting dial
Max. : maximum frequency (Refer to P03, 15)
Min. :Minimum frequency (or 0V stop)
Set with the "Fr mode" using the MODE,
SET buttons.
Terminals No. 1, 2, 3 (connect potentiometer's
center tap to 2)
Terminals No.2 and 3 (2:+,3:–)
Terminals No.2 and 3 (2:+,3:–)
Terminals No. 2 and 3, (2:+,3:–)
Connect 200Ω across 2-3
,
and
40