Drive Programming Editor; Executing A Program - Omron 3G3MX2 Series User Manual

Drive programming
Hide thumbs Also See for 3G3MX2 Series:
Table of Contents

Advertisement

9-3

Drive Programming Editor

9-3-1

Executing a Program

You execute the program by setting the inverter parameter, the Drive Programming Function Selection
(F025).
Once the program reaches "end" command after a series of processes was completed, the program is
not executed unless it is restarted.
To repeat the program, create a loop program so that the program does not reach "end" command.
Parameter
Function name
No.
F025
Drive Programming
Function Selection
F026
Drive Programming
RUN Trigger Selection
C001 to
Multi-function Input S1
C007
to S7 Selection
Drive Programming User's Manual (I580-E2)
Data
00: Disabled (default setting)
01: Enabled
(Start/stop at power on/off)
00: TRM ("PRG" terminal)
01: PARAM (setting F025 =
enable)
76: PRG
(Drive Programming start)
9 LX inverter
Description
Disables the Drive Programming function.
Programs are not executed.
If you change the setting to 00 (Disabled)
during program execution, the program
will be stopped.
Starts the Drive Programming program
automatically after the inverter power sup-
ply is turned on.
If you change the setting to 01 (Enabled)
while the program is stopped, the program
will be started.
Drive Programming program will run by
terminal. Set terminal to PRG function.
Drive Programming program will run if
F025 = enable
When the Drive Programming Function
Selection (F025) is set to 01 (Enabled:
Start/stop at power on/off), the program is
started via the multi-function input terminal
with this setting.
9
9 - 5