Advertisement

5 Drive Programming User Variables
5-5

Inverter Monitor Variables

You can use the inverter's internal monitor function and status monitor function as the variables of the
Drive Programming function.
For details on each monitor function, refer to the MX2 User's Manual (I570-E2) or the RX User's Manual
(I560-E2).
Note that the data unit used for the inverter may be different from that for Drive Programming. Be sure
to use the following units.
 MX2 and RX
Function
variable
FM
Output Frequency Monitor
[d001]
Use this function to monitor the inverter output frequency. The monitored data is equivalent to the data
of the Output Frequency Monitor (d001). This variable is read-only.
Function
variable
Iout
Output Current Monitor
(d002)
Use this function to monitor the inverter output current. The monitored data is equivalent to the data of
the Output Current Monitor (d002). The data is displayed in increments of 0.1% as a percentage of the
rated current of the inverter. This variable is read-only.
Function
variable
Dir
RUN Direction Monitor
(d003)
Use this function to monitor the operation direction of the inverter. The monitored data is equivalent to
the data of the RUN Direction Monitor (d003). This variable is read-only.
Function
variable
PID-FB
PID Feedback Value Monitor
(d004)
Use this function to monitor the PID feedback value. The monitored data is equivalent to the data of the
PID Feedback Value Monitor (d004). This variable is read-only.
Function
variable
F-CNV
Output Frequency Monitor
(After Conversion) (d007)
Use this function to monitor the output frequency after conversion. The monitored data is equivalent to
the data of the Output Frequency Monitor (After Conversion) (d007). This variable is read-only.
5 - 14
Description
Data range
0 to 40,000
Description
Data range
0 to 9,999
Description
Data range
0: Stop
1: Forward
2: Reverse
Description
Data range
0 to 133,333
Description
Data range
0 to 3,999,600
Default
Unit
Data size
data
0.01 Hz
Unsigned
1 word
Default
Unit
Data size
data
0.1%
Unsigned
1 word
Default
Unit
Data size
data
Unsigned
1 word
Default
Unit
Data size
data
0.01%
Unsigned
2 words
Default
Unit
Data size
data
0.01
Unsigned
2 words
Drive Programming User's Manual (I580-E2)
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R