Omron 3G3MX2 Series User Manual page 33

Drive programming
Hide thumbs Also See for 3G3MX2 Series:
Table of Contents

Advertisement

3 Operation Procedure for Drive Programming
Downloading Programs
Download compiled programs to the inverter and save them in the EEPROM of the inverter.
You can start programs saved in the EEPROM after turning on the power supply, without using the tool
(CX-Drive).
Selecting Drive Programming Functions
Set Drive Programming Function Selection (A017) to Enabled (01 or 02) to use the Drive Programming
function. You can change the Drive Programming Function Selection (A017) even when the operation is
in progress.
Parameter
Function name
No.
A017
Drive Programming
Function Selection
*1. Multi-function input terminals for MX2 are S1 to S7, and for RX are S1 to S8.
Starting Programs
When the Drive Programming Function Selection (A017) is set to 01 (Enabled: Start/stop via multi-func-
tion input PRG terminal), set one of Multi-function Input S1 to S7/S8 Selection to 82 (PRG). The pro-
gram is started when the multi-function input terminal set to PRG is turned ON. The program execution
continues while the PRG terminal is ON and stops when the terminal is turned OFF.
When the Drive Programming Function Selection (A017) is set to 02, the program is started right after
the setting is completed. The program will also be started automatically at next power on.
Once the program reaches "end" command after it was started and a series of processes was com-
pleted, the program is not executed unless it is restarted.
To repeat the program, create a loop program so that the program does not reach "end" command.
The downloaded Drive Programming program is saved in the EEPROM of the inverter. Therefore, after
downloading, you can start the program without using the support tool.
Parameter
Function name
No.
C001 to
MX2 and RX:
C007
Multi-function Input S1
to S7 Selection
C008
RX only:
Multi-function Input S8
Selection
3 - 4
Data
00: Disabled (default
Disables the Drive Programming function.
setting)
Programs are not executed.
If you change the setting to 00 (Disabled) during
program execution, the program will be stopped.
01: Enabled
Starts the Drive Programming program when the
(Start/stop via
multi-function input terminal
multi-function input
(PRG) is turned ON.
PRG terminal)
02: Enabled
Starts the Drive Programming program automati-
(Start/stop at
cally after the inverter power supply is turned on.
power on/off)
If you change the setting to 02 (Enabled) while the
program is stopped, the program will be started.
Data
82: PRG
(Drive Programming start)
Description
*1
which is set to 82
Description
When the Drive Programming Function
Selection (A017) is set to 01 (Enabled:
Start/stop via multi-function input PRG
terminal), the program is started via the
multi-function input terminal with this setting.
Drive Programming User's Manual (I580-E2)