Pr. 577
Output frequency
Fig. 5-270:
When the PID output shutoff release level is reached during a deceleration stop, output shutoff is
released, operation is re-accelerated and PID control is continued. During deceleration Pr. 576
"Output interruption detection level" is invalid.
Integral stop selection at limited frequency (Pr. 1015)
The operation for the integral term can be selected when the frequency is restricted by the upper/
lower limit, or the manipulated amount is limited to ±100% during PID control.
The operation during output shutoff can be selected for the integral term using the PID output sus-
pension function (SLEEP function).
Pr. 1015 setting
0 (initial value)
1
10
11
Tab. 5-230: Pr. 1015 settings
FR-A800
When Pr. 554 = "10 to 13", reverse operation (Pr. 128 = "10")
Deviation
1000%
Pr. 576
Less than Pr. 575
RUN
PID
SLEEP
Output interruption (SLEEP function)
Operation at limited frequency
Integral stop
Integral continuation
Integral stop
Integral continuation
Deceleration stop
SLEEP period
Pr. 575 or more
OFF
ON
(A) Application parameters
Cancel
level
Time
Operation during output
interruption
Integral clear
Integral clear
Integral stop
Integral stop
I002694E
5 - 555