(M) Monitor display and monitor output signal
● When Pr. 54 "FM/CA terminal function selection" = "87, 88, 89, or 90" (remote output), the CA type
inverter can output any analog current from the terminal CA.
● Terminal CA output [mA] = 20 [mA] × (analog remote output value – 1000)/100
Where the output range is 0 to 20 mA.
Fig. 5-185:
● When Pr. 158 "AM terminal function selection" = "87, 88, 89, or 90", an analog voltage can be output
from the terminal AM.
● Terminal AM output [V] = 10 [V] × (analog remote output value – 1000)/100
The output range is –10 V to +10 V regardless of the Pr. 290 "Monitor negative output selection"
setting.
Fig. 5-186:
5 - 400
Output current [mA]
800
Terminal CA output
Output voltage [V]
800
900
Terminal AM output
20
0
1000
1100
Analog remote output value [%]
Terminal CA
10
0
1000
1100
Analog remote output value [%]
-10
Terminal AM
Parameters
1200
I002634E
1200
I002635E