Parameters
Ethernet communication network number (Pr. 1424),
Ethernet communication station number (Pr. 1425)
When the MELSOFT / FA product connection, SLMP, or iQSS is selected for Ethernet communication,
enter the Ethernet communication network number in Pr. 1424 and the Ethernet communication sta-
tion number in Pr. 1425.
5.15.9

MELSOFT / FA product connection

FR Configurator2, GOT, or a relay station (programmable controller) can be connected via Ethernet.
Initial setting
● Set any value from "5000 to 5002, 5006 to 5008" in any of Pr. 1427 to Pr. 1429 (Ethernet function
selection 1 to 3) to select the MELSOFT / FA product connection for the application. (For how to
set the application value, refer to the Instruction Manual of the device connected via Ethernet.)
(Refer to page 5-677.)
● Enter the Ethernet communication network number in Pr. 1424 and the Ethernet communication
station number in Pr. 1425. (Refer to page 5-683.)
● Enable the PLC function (Pr. 414 "PLC function operation selection" ≠ "0 (initial value)") to use FR
Configurator2 (Developer). (For the details of Pr. 414, refer to page 5-606.)
System configuration
Direct connection with FR Configurator2
Direct connection with GOT
Connection using a relay station
(programmable controller)
Fig. 5-336:
FR-A800
MELSOFT / FA product connection system configuration
(N) Operation via communication and its settings
Ethernet cable
Personal computer
(FR Configurator2)
Ethernet cable
GOT
Relay station
(programmable controller)
Inverter
Inverter
Ethernet cable
Inverter
I003115E
5 - 683