Mitsubishi Electric FR-A820-00046 Instruction Manual page 968

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

CC-Link IE Field Network (FR-A800-GF)
Programming example for the parameter writing
The following program changes the setting value in Pr. 7 "Acceleration time" of the station 1 inverter
to 3.0 s.
● Acceleration time writing instruction code: H87 (hexadecimal)
● Acceleration time setting data: K30 (decimal)
For the details of instruction codes of each parameter, refer to the list of parameters (function codes)
and instruction codes under different control methods on page A-5.
The reply code (RWr10) to the instruction code execution is set in D2.
(Refer to page 5-756 for the reply code (RWr10).)
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302
X1025
18
24
Fig. 5-379:
Programming example 5
NOTES
For the parameter assigned the number of 100 or higher, change the link parameter extended set-
ting (set it to the one other than H00). Refer to page A-5 for the settings.
For other functions, refer to the instruction codes on page 5-757.
5 - 766
Check the data link status of the station 1.
M0
PLS M300
SET M301
MOV H87 W110
Write the Pr. 7 write code (H87) to RWw10 and the acceleration time
setting data (K30) to RWw11.
MOV K30 W111
Turn ON the instruction code execution request (RY25).
SET Y1025
RST M301
SET M302
Read the reply code (RWr10) to output to D2 when the instruction code
MOV W10 D2
execution completion (RX25) turns ON.
RST Y1025
Turn OFF the instruction code execution request (RY25).
RST M302
END