Mitsubishi Electric FR-A820-00046 Instruction Manual page 1005

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
NOTES
To use the CC-Link IE Field Network Basic, do not install the FR-A8NC to the inverter. (Doing so dis-
ables communication through the CC-Link IE Field Network Basic.)
When the CC-Link IE Field Network Basic is used, a communication error (E.EHR) occurs regardless
of the Pr. 1432 "Ethernet communication check time interval setting" in the following cases: the
data addressed to the own station is not received for the predetermined timeout period or longer,
or the status bit of the cyclic transmission addressed to the own station turns OFF (when the mas-
ter gives a command to stop the cyclic transmission). (For the details of the timeout period, status
bit of the cyclic transmission, and command to stop the cyclic transmission, refer to the Instruction
Manual of the master controller which supports the CC-Link IE Field Network Basic.)
CC-Link extended setting (Pr. 544)
Use this parameter to select the function of the remote registers for the CC-Link IE Field Network Basic.
Pr. 544 setting
0 (initial setting)
1
12
14
18
24
28
100
112
114
118
128
Tab. 5-386: Pr. 544 settings
FR-A800
Description
Compatible with CC-Link Ver.1
Compatible with CC-Link Ver.1
Compatible with the double setting of CC-Link Ver.2
Compatible with the quadruple setting of CC-Link Ver.2
Compatible with the octuple setting of CC-Link Ver.2
Compatible with the quadruple setting of CC-Link Ver.2
Compatible with the octuple setting of CC-Link Ver.2
Compatible with CC-Link Ver.1
Compatible with the double setting of CC-Link Ver.2
Compatible with the quadruple setting of CC-Link Ver.2
Compatible with the octuple setting of CC-Link Ver.2
Compatible with the octuple setting of CC-Link Ver.2
Ethernet communication (FR-A800-E)
Refer to page
5-805
5-806
5-807
5-808
5-809
5-808
5-809
Refer to the
PLC function
PLC function
programming
manual.