Ethernet communication (FR-A800-E)
● Remote RUN
The external device executes the remote RUN to the inverter.
– Request data
Item
Mode
Clear mode
Tab. 5-364: Request data description for remote RUN instruction
– Response data
None
● Remote STOP
The external device executes the remote STOP to the inverter.
– Request data
– Response data
None
● CPU (inverter) model name read
The external device reads the model name and model code of the inverter.
– Request data
– Response data
Item
Model
Model code
Tab. 5-365: Response data description for reading the model name
5 - 784
Mode
H01 H10 H00 H00
Description
Forced execution of the remote RUN is not allowed.
Forced execution of the remote RUN is allowed.
Devices are not cleared (initialized).
Devices are cleared.
H02 H10 H00 H00 H01 H00
H01 H01 H00 H00
Description
The inverter model is stored. Up to 16 characters can be stored. If the model name is
shorter than 16 characters, a space (H20) is stored instead of a character.
Example:
FR-A800-E inverter: FR-A800-E
Fixed to H054E
Clear
mode
H00
Model
Parameters
H0100
H0300
H00
H01, H02
Model
code

Hide quick links: