Mitsubishi Electric FR-A820-00046 Instruction Manual page 970

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

CC-Link IE Field Network (FR-A800-GF)
Programming example for the fault record reading
The following program reads the fault records of the station 1 inverter to output to D1.
● Faults history No. 1 and 2 reading instruction code: H74 (hexadecimal)
For the error code, refer to page 6-5.
The reply code (RWr10) to the instruction code execution is set in D2.
(Refer to page 5-756 for the reply code (RWr10).)
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302 X1025
16
24
Fig. 5-381:
Programming example for resetting the inverter at an inverter fault
The following program resets the station 1 inverter at an inverter fault.
SB49
SW0B0.0
0
M0 X103A X20
3
Error status flag
7
Fig. 5-382:
NOTES
The inverter reset with the flag RY3A shown above is enabled at an inverter fault only.
When Pr. 349 "Communication reset selection" = "0", an inverter reset can be made in any opera-
tion mode.
When using the instruction code execution request (RY25) with the instruction code (HFD) and
data (H9696) to reset the inverter, set a value other than "0" in Pr. 340 "Communication startup
mode selection" or change the operation mode to the Network operation mode. (Refer to pro-
gram example 2 on page 5-763).
5 - 768
PLS M300
SET M301
MOV H74
SET Y1025
RST M301
SET M302
MOV W11 D1
MOV W10 D2
RST Y1025
RST M302
Programming example 7
Programming example 8
Check the data link status of the station 1.
M0
Write the faults history No.1 and No.2 read code (H74) to
W110
RWw10.
Turn ON the instruction code execution request (RY25).
Read the fault record (RWr11) and the reply code (RWr10)
to output to D1 and D2 when the instruction code
execution completion (RX25) turns ON.
Turn OFF the instruction code execution request (RY25).
END
Check the data link status of the station 1.
M0
Turn ON the error reset request flag (RY3A).
Y103A
Turn OFF the error reset request flag (RY3A) when the error
status flag (RX3A) is OFF.
END