Mitsubishi Electric FR-A820-00046 Instruction Manual page 158

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Power supply harmonics
● Calculation of outgoing harmonic current
Outgoing harmonic current
= fundamental wave current (value converted from received power voltage)
× operation ratio × harmonic content
– Operation ratio:
– Harmonic content: Found in tab. 3-10.
Applica-
ble motor
[kW]
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
Tab. 3-11:
Applica-
ble motor
[kW]
75
90
110
132
160
220
250
280
315
355
400
450
500
560
630
Tab. 3-12:
3 - 14
Operation ratio = actual load factor × operation time ratio during 30 minutes
Fundamental
Fundamen-
wave current
tal wave
(A)
current con-
verted from
200 V 400 V
6.6 kV [mA]
1.61
0.81
49
2.74
1.37
83
5.50
2.75
167
7.93
3.96
240
13.0
6.50
394
19.1
9.55
579
25.6
12.8
776
36.9
18.5
1121
49.8
24.9
1509
61.4
30.7
1860
73.1
36.6
2220
98.0
49.0
2970
121
60.4
3660
147
73.5
4450
180
89.9
5450
Rated capacities and outgoing harmonic currents (no reactor) of inverter-driven motors
Fundamental
Fundamen-
wave current
tal wave
(A)
current con-
verted from
200 V 400 V
6.6 kV [mA]
245
123
7455
293
147
8909
357
179
10848
216
13091
258
15636
355
21515
403
24424
450
27273
506
30667
571
34606
643
38970s
723
43818
804
48727
900
54545
1013
61394
Rated capacities and outgoing harmonic currents (with DC reactor) of inverter-driven
motors
Outgoing harmonic current converted from 6.6 kV [mA]
Rated
(No reactor, 100% operation ratio)
capacity
[kVA]
5th
7th
11th
0.57
31.85
20.09
4.165
0.97
53.95
34.03
7.055
1.95
108.6
68.47
14.20
2.81
156.0
98.40
20.40
4.61
257.1
161.5
33.49
6.77
376.1
237.4
49.22
9.07
504.4
318.2
65.96
13.1
728.7
459.6
95.29
17.6
980.9
618.7
128.3
21.8
1209
762.6
158.1
25.9
1443
910.2
188.7
34.7
1931
1218
252.5
42.8
2379
1501
311.1
52.1
2893
1825
378.3
63.7
3543
2235
463.3
Outgoing harmonic current converted from 6.6 kV [mA]
Rated
(With a DC reactor, 100% operation ratio)
capacity
[kVA]
5th
7th
11th
87.2
2237
969
626
104
2673
1158
748
127
3254
1410
911
153
3927
1702
1100
183
4691
2033
1313
252
6455
2797
1807
286
7327
3175
2052
319
8182
3545
2291
359
9200
3987
2576
405
10382
4499
2907
456
11691
5066
3274
512
13146
5696
3681
570
14618
6335
4093
638
16364
7091
4582
718
18418
7981
5157
Precautions for use of the inverter
13th
17th
19th
23rd
3.773
2.107
1.519
1.274
6.391
3.569
2.573
2.158
12.86
7.181
5.177
4.342
18.48
10.32
7.440
6.240
30.34
16.94
12.21
10.24
44.58
24.90
17.95
15.05
59.75
33.37
24.06
20.18
86.32
48.20
34.75
29.15
116.2
64.89
46.78
39.24
143.2
79.98
57.66
48.36
170.9
95.46
68.82
57.72
228.7
127.7
92.07
77.22
281.8
157.4
113.5
95.16
342.7
191.4
138.0
115.7
419.7
234.4
169.0
141.7
13th
17th
19th
23rd
373
350
239
224
445
419
285
267
542
510
347
325
655
615
419
393
782
735
500
469
1076
1011
688
645
1221
1148
782
733
1364
1282
873
818
1533
1441
981
920
1730
1627
1107
1038
1949
1832
1247
1169
2191
2060
1402
1315
2436
2290
1559
1462
2727
2564
1746
1636
3070
2886
1965
1842
25th
0.882
1.494
3.006
4.320
7.092
10.42
13.97
20.18
27.16
33.48
39.96
53.46
65.88
80.10
98.10
25th
164
196
239
288
344
473
537
600
675
761
857
964
1072
1200
1351