Per Output For Function Staircase Light - ABB i-bus KNX Product Manual

Light controller with sensor lr/s with lf/u, intelligent installation systems
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
3.3.8
Per output for function
Staircase light
© 2008 ABB STOTZ-KONTAKT GmbH
Commissioning
No.
Function
24, 49,
Activate staircase function
1
74, 99
This object is enabled if in parameter window
Staircase light is enabled.
The Staircase lighting function can be activated or deactivated via this object. With a
deactivated staircase lighting function the output of the device behaves like a "normal"
output of a Switch / Dim actuator. The staircase lighting function is again activated if
the value 1 is received via the object described here.
If the staircase lighting is switched off at the time when it is activated, the base brightness
is set. If the lighting is switched on at the time, the staircase light brightness is set and the
staircase light time times out.
After bus voltage recovery the staircase lighting function is always activated. By setting
the T flag the object is actively sent after bus voltage recovery.
Telegram value:
0 = staircase lighting function not activated
1 = activate staircase lighting function
25, 50,
Permanent ON
1
75, 100
This object is enabled if in parameter window
Staircase light is enabled.
Serves as an active staircase light control for permanent switch on of the lighting (also called
"Service light").
After a bus voltage recovery or download the object value is set to 0 and a permanent on
is not active.
Telegram value:
0 = Permanent ON not active
1 = Permanent ON active
26, 51,
Duration of staircase lighting
1
76, 101
This object is enabled if in parameter window
Staircase light is enabled.
Via this object the staircase lighting time can be set via the KNX. The time (counter value)
is defined in seconds. After bus voltage recovery the object value is accepted by the
programmed value in the ETS and the value set via the bus is lost.
27, 52,
Warning staircase lighting
1
77, 102
This object is enabled if in parameter window
Staircase light is enabled.
The value of the object is used to provide a warning before the staircase lighting time times
out. The object has the value 1 during the warning.
If a forced operation is activated during the prewarning, the prewarning is reset and a 0 is
written into the object Warning staircase lighting and a telegram with the value 0 is sent on
the KNX.
1)
The numbers of the objects apply for outputs A to D.
Object name
Data type
1 bit (EIS1)
Output X
DPT 1.003
in parameter additional function
X: General
1 bit (EIS1)
Output X
DPT 1.001
in parameter additional function
X: General
2 byte (EIS 10)
Output X
DPT 7.005
in parameter additional function
X: General
1 bit (EIS 1)
Output X
DPT 1.005
in parameter additional function
X: General
Flags
C, W
C, W
C, R, W
C, T