ABB i-bus KNX Product Manual page 55

Light controller with sensor lr/s with lf/u, intelligent installation systems
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
© 2008 ABB STOTZ-KONTAKT GmbH
Commissioning
Reaction on preset 2 (telegr. value 1)
Options:
100/99...1/0 %
This parameter determines the brightness value which is controlled with a
recall of preset 2 (= object Call preset 1 and 2 receives a telegram value 1).
At the same time with the first call of preset 2, the state of the output is
saved so that the corresponding parameterisation of the value before preset
2 can be restored.
Time to set new brightness value
"Transition time" in s [0...65,535]
Options:
0...65,535
This parameter defines the time in which a preset recall is dimmed to
the new brightness value.
Preset 1 and 2 can be set via the bus
Options:
no
yes
This parameter enables the object Set preset 1 and 2. It is thus possible to
store the currently set brightness value as the new preset value.
Telegram value 0 saves preset 1, whereas telegram value 1 saves preset 2.
53