Commissioning
No.
Function
10, 35,
Switch/Status
1
60, 85
The object is enabled if in the parameter window
via the object Switch/Status.
This object has the same functions and characteristics as the object Switch. The status
is additionally fed back. If only one common object for switching and feedback is used,
no inversion of the feedback is possible.
Telegram value:
0 = OFF command: relay opens
1 = ON command: relay closes
Note
If several groups are assigned to the object Switch/Status, the status
address should be set as the sending address. In a KNX groups with several
status feedback messages, it is useful to allow just a single group member to
feedback the status.
11, 36,
Status switch
1
61, 86
This object is released if the parameter Status response of the switching state in the
parameter window
X: General
The object value directly indicates the current contact position of the switching relay.
An inversion of the status value as when sending the status telegram can be parameterised.
The status can only be sent with a change, or with a change and triggered by a switch
command. The parameterisation if value change and triggered by switch command which is
sent with a change and also with the receipt on every input of a telegram on the object
Switch or Switch/Status. Other switch actions, e.g. by scene or preset recalls only trigger
sending of the status with a status change.
Manual switching is not detected so that in this case the status message does not
correspond with the contact position.
12, 37,
Relative dimming
1
62, 87
The object is always enabled in order to enable dimming without parameterisation.
The relative dimming telegram for the corresponding output is received via this object. It is a
dim command (BRIGHTER, DARKER, STOP). After a start command is received the
brightness value is changed in the defined direction with the parameterised speed. If a stop
command is received before the dim process ends or the maximum or minimum dimming
value is reached, the dimming process is interrupted and the received brightness value is
retained.
Dim values which are above or below the max. or min. dimming values will not be received,
the parameterised max. or min. dimming values remain as they are with further dimming.
Object name
Output A
X: General
Output A
has the value yes: via a separate object Switch status.
Output A
Data type
Flags
1 bit (EIS 1)
C, R, W, T
DPT 1.001
the feedback is parameterised
1 bit (EIS 1)
C, R, T
DPT 1.001
4 bit (EIS 2)
C, W
DPT 3.007
85