ABB i-bus KNX Product Manual page 57

Light controller with sensor lr/s with lf/u, intelligent installation systems
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
© 2008 ABB STOTZ-KONTAKT GmbH
Commissioning
With the recall of light scenes the maximum and minimum values as
set in the parameter window
limits are set when the maximum and minimum values are overshot or
undershot. At a brightness value of 0, a switch off is always executed,
independently of the parameter Allow switching off via brightness
value parameterised in the parameter window X: Value.
A scene recall as well as saving of a scene has no effect on
the output with parameterised staircase lighting function.
The reaction to the scene recall with parameterised slave mode can
be parameterised in the
reaction parameterisation a scene recall is ignored with active slave
mode. The parameterisation Slave mode can be deactivated has
the effect that the scene recall as well as a scene store command
are implemented and the slave operation discontinued.
Note
The slave operation has no effect but is active in the background
and can be reactivated by an ON command telegram with the value
1 to the object Switch. For this reason the first bit of the status byte
has the value 1. Furthermore, the slave mode can be activated via
the object Activate slave mode.
The reaction to a scene command with active light control can be
parameterised in the parameter window
Assignment to scene number 1...64
Options:
no assignment
Scene no. 1
...
Scene no. 64
In this parameter the output is assigned to a scene number (1...64).
As soon as the device receives a telegram with this scene number on
the object 8 bit scene, it will recall the corresponding scene.
Standard brightness value
Options:
100/99...1/0 %
This parameter defines the brightness value which the output controls
with a scene recall.
The value parameterised here can be changed. This is implemented
by "setting" a scene. Via the object Restore standard scene the value
can be reset again to the parameterised value. It can be set in
parameter window
values with standard values.
Time to set new brightness value
"Transition time" in s [0...65,535]
Options:
0...3...65,535
With this parameter the transition time which is required until
the scene brightness value is reached is set.
apply. The values of the value
X: Value
parameter window. With the no
X: Slave
X: Control
with the parameter Restore scene
X: Function
Operating.