Commissioning
Enable function 8 bit scene
Options:
no
yes
With this parameter the output can be enabled for an 8 bit scene.
This function enables the recall or saving of up to 64 scenes via a 1 byte
object. Project-specific, manually set brightness values can be saved via
the 1 byte object 8 bit scene. Every output of the Light Controller can be
integrated in up to 15 scenes with any standard brightness values and
transition times.
Yes: A further parameter appears:
Restore scene values with standard values
Options:
no
via download
via object "restore standard scene"
via download or via object
This parameter defines if the brightness values allocated to the
scenes currently in the device are overwritten by the brightness
values in the ETS.
This function is useful for example, if the scene settings of the user
are to be undone.
The reset of the scene values are possible via an ETS download or
via object restore standard scene.
The special properties of the 8 bit scene are defined in the
parameter window. Every output of the Light Controller
X: Scene (x)
can be integrated in up to 18 scenes.
Enable function "forced operation"
Options:
no
1 bit control
2 bit control
With this parameter the output can be enabled for forced operation.
1 bit control: A 1 bit Forced operation object is enabled. If the Light
Controller receives a telegram with the value 1 via this object, the output
of the Light Controller is forcibly operated. With the value 0 the forced
operation is rescinded and the output is once again released.
Both the following parameters are enabled with parameterised
1 bit control :
Brightness while object value = 1
(forced operation = active, ON)
Options:
100 % (255), 99 % (252)...0 % (Off)
The brightness value applied for switching on the lighting of the output
during activated forced operation, can be parameterised with this
parameter. Forced switch off of the output is also parameterised.
40