Per Output - ABB i-bus KNX Product Manual

Light controller with sensor lr/s with lf/u, intelligent installation systems
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
3.3.2

Per output

© 2008 ABB STOTZ-KONTAKT GmbH
Commissioning
With corresponding parameterisation the objects Switch/Status and Brightness value/Status
appear.
No.
Function
10, 35,
Switch
1)
60, 85
The object is always enabled in order to immediately switch on and off without
parameterisation.
This object is used for switching an output ON/OFF.
Telegram value:
0 = OFF command: relay opens
1 = ON command: relay closes
If the staircase light function is activated, the staircase light is switched on via this object.
An inversion is not intended.
The relay only always receives a switch impulse, if a calculated contact change is required,
i.e. a repeated switch command is not carried out again. .
This behaviour should be considered particularly with a manual operation of the relay.
This action is not recognised by the Light Controller and is therefore not considered in the
contact calculation. For this reason a manually switched off contact can only be switched on
via the bus if an off command has been received via the bus beforehand.
It is possible to parameterise that the switch status is fed back via the object Switch or via
the object Switch/Status. Generally the feedback uses a separate object Status switch for
this purpose. In the parameter window
or two separate objects are available for the switch and feedback. An inversion of the switch
status can also be parameterised.
1)
The numbers of the objects apply for outputs A to D.
Object name
Data type
1 bit (EIS 1):
Output A
DPT 1.001
you can parameterise if a common object
X: General
Flags
C, W, T
84