5 Advanced Operations
Simple programming is used.
The related parameters are as follows:
Program pattern: STOP
Soak time = 10 min
Wait band: 3
Set point
RSET → STRT
Operating Procedure
• Setting the Program Pattern
1
Press the M Key several times in the Initial Setting Level to
display ptrm (Program Pattern).
2
Press the U or D Key to select stop (STOP).
The default is off.
• Setting the Soak Time
1
Press the M Key several times in the Adjustment Level to dis-
play soak (Soak Time).
2
Press the U or D Key to set the value to 10.
The default is 1 (min or h).
• Setting the Wait Band
1
Press the M Key several times in the Adjustment Level to dis-
play wt-b (Wait Band).
2
Press the U or D Key to set the value to 3.0.
The default is off.
5 - 42
PV
Soak time = 10 min
Wait band = 3
END display
END output
STOP
E5@C Digital Temperature Controllers User's Manual (H174)
Initial Setting Level
ptrn
Program Pattern
off
ptrn
stop
Adjustment Level
soak
Soak Time
1
soak
10
Adjustment Level
wt-b
Wait Band
off
wt-b
3.0