Settings

To execute ON/OFF control, set the Set Point, PID ON/OFF, and Hysteresis parameters.
Setting the PID ON/OFF Parameter
Confirm that the PID ON/OFF parameter is set to onof in the Initial Set-
ting Level.
Operating Procedure
1
Press the M Key several times in the Initial Setting Level to
display cntl (PID ON/OFF).
The default is onof (ON/OFF control).
Setting the SP
In this example, the set point is set to 200°C. The set value (i.e., the SP)
is shown at the bottom of the display.
Operating Procedure
1
Select PV/SP in the Operation Level.
2
Press the U or D Key to set the SP to 200.
The default is 0.
The new set value can be saved by pressing the M Key, or it will go
into effect after 3 seconds has elapsed.
4 - 22
Parameter
Standard or
Specifying control
Heating/Cooling
method
PID ON/OFF
Specifying control
method
Direct/Reverse
Specifying control
Operation
method
Dead Band
Heating/cooling
control
Hysteresis (Heating)
ON/OFF control
Hysteresis (Cooling)
ON/OFF control
Application
Level
Initial Setting Level
Initial Setting Level
Initial Setting Level
Adjustment Level
Adjustment Level
Adjustment Level
E5@C Digital Temperature Controllers User's Manual (H174)
Initial Setting Level
cntl
PID ON/OFF
onof
Operation Level
25
PV/SP
100
25
200