5-14-3 Application Example Using a Simple Program

The program will be started by changing the setting of the Program Start parameter. The following
example shows using a simple program with the program pattern set to STOP.
Set point
END display
END output
RUN/STOP
status
Program
start
Timing
(1)
• The Program Start parameter was changed from RSET to STRT using either an event or key
operations.
• The RUN/STOP status automatically changes to RUN mode when the above operation is per-
formed.
(2)
• The Program Start parameter was changed from STRT to RSET using either an event or key
operations before the soak time expired.
• The RUN/STOP status automatically changes to STOP mode when the above operation is per-
formed.
(3)
• The Program Start parameter is again changed from RSET to STRT using either an event or key
operations.
• The RUN/STOP status will automatically change to RUN mode when the above operation is per-
formed.
(4)
• The RUN/STOP status automatically changes to STOP mode when soak time expires.
• END flashes on the No. 2 display and the program END output turns ON.
(5)
• The Program Start parameter is changed from STRT to RSET using either an event or key oper-
ations.
• The END display is cleared and the program END output turns OFF.
(6)
• Key operations are used to switch the RUN/STOP status to RUN with the Program Start parame-
ter set to RSET (stopped).
• Normal control operation is started.
(7)
• The Program Start parameter is changed from RSET to STRT using either an event or key oper-
ations after the process value stabilizes.
• The RUN/STOP status remains as RUN.
(8)
• Key operations are used to change the RUN/STOP status to STOP (during program operation).
• Measuring the soak time is continued within the wait band. (Measuring the soak time stops when
the process value leaves the wait band.)
(9)
• Key operations are used to change the RUN/STOP status to RUN.
• Measuring the soak time is continued within the wait band (continuing from the time between (7)
and (9)).
(10)
• The RUN/STOP status automatically changes to STOP mode when the measured time reaches
the soak time.
• END flashes on the No. 2 display and the program END output turns ON.
E5@C Digital Temperature Controllers User's Manual (H174)
PV
Soak time
RSET
STRT
STRT
(1)
(2)
(3)
(4)
(5) (6)
5 Advanced Operations
Soak time
Soak time
STOP
RUN
RUN
RSET
STRT
(7) (8) (9)
(10)
Description
Wait band
5 - 43