Sometimes an error occurs between the process value and the actual temperature. To offset
this, a compensated value can be obtained by adding an input shift value to the input. The
compensated value is displayed as the process value and used for control. The entire input
Function
range is shifted by a fixed rate. If the input shift value is set to −1°C, control will be per-
formed for a value 1°C lower than the measured temperature.
Temperature input: −199.9 to 999.9
Setting
Analog input: −1,999 to 9,999*
*
Related Parameters
See
See
Input Type (Initial Setting Level): Page 6-42
inrt
This parameter sets a factor to apply to the input to compensate the process value. The
resulting value is displayed as the process value and used in control.
Function
Setting
rss
This parameter sets a compensation value to add to the remote SP input to compensate it.
The compensated value is displayed as the process value and used in control.
Function
Temperature input: −199.9 to 999.9
Setting
Analog input: −1,999 to 9,999
*
Related Parameters
See
See
Input Type (Initial Setting Level): Page 6-42
E5@C Digital Temperature Controllers User's Manual (H174)
Process Value Input Shift
Setting range
The decimal point position depends on the Decimal Point parameter setting.
Process Value Slope Coefficient
Setting range
0.001 to 9.999
000
Remote SP Input Shift
Setting range
The decimal point position depends on the Decimal Point parameter setting.
Unit
°C or °F
EU
000
Default
1.000
There must be a remote SP input.
Unit
°C or °F
EU
6 Parameters
Default
0.0
0
Default
0.0
0
6 - 27
6