Omron E5CC User Manual page 52

Digital
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

2 Preparations
Output type
RX
Relay output
QX
Voltage output (for driving SSR)
CX
Current output
RR or
2 relay outputs
PR
QQ*
2 voltage outputs (for driving
SSRs)
QR
Voltage output (for driving SSRs)
(control output 1)
Relay output (control output 2)
CC*
2 current outputs
CQ*
Current output (control output 1)
Voltage output (for driving SSR)
(control output 2)
*
Control output 1 and control output 2 are not isolated.
Auxiliary Outputs 1 to 4
When heating/cooling control is used on the E5CC, auxiliary output 2 is the control output for cooling. When
heating/cooling control is used on the E5EC/E5AC, auxiliary output 4 is the control output for cooling unless the
Controller has only two auxiliary outputs, in which case auxiliary output 2 is the control output for cooling.
Event Inputs
Models with an option number of 001 or 004 to 014 have event inputs.
E5CC
Option number: 001, 006, or 007
Option number: 004
2 - 18
Specification
SPST-NO, 250 VAC, 5 A (resistive load), Electrical
durability: 100,000 operations
PNP, 12 VDC ±20%, 40 mA (with short-circuit protection)
4 to 20 or 0 to 20 mA DC, Load: 500 Ω max., Resolution:
Approx. 10,000
SPST-NO, 250 VAC, 5 A (resistive load), Electrical
durability: 100,000 operations
PNP, 12 VDC ±20%, 21 mA (with short-circuit protection)
PNP, 12 VDC ±20%, 21 mA (with short-circuit protection)
SPST-NO, 250 VAC, 5 A (resistive load), Electrical
durability: 100,000 operations
4 to 20 or 0 to 20 mA DC, Load: 500 Ω max., Resolution:
Approx. 10,000
4 to 20 or 0 to 20 mA DC, Load: 500 Ω max., Resolution:
Approx. 10,000
PNP, 12 VDC ±20%, 21 mA (with short-circuit protection)
Contact inputs
13
14
EV1
EV2
15
16
EV3
17
EV4
18
Non-contact inputs
13
EV1
14
+
EV2
15
+
16
EV3
17
+
EV4
18
+
E5@C Digital Temperature Controllers User's Manual (H174)

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5acE5ec

Table of Contents