5 Advanced Operations
5-9

OR Output of Alarms

5-9-1

Integrated Alarm

You can use an integrated alarm to output an OR of alarms 1 to 4, the HB alarm, the HS alarm, the
input error, and the RSP input error. Set the Integrated Alarm Assignment parameter (alma) and then
assign the integrated alarm (alm) to an auxiliary output or a control output.
Parameters
Parameter
Control Output
Assignment
Auxiliary
Output 1 to 4
Assignment
Integrated
Alarm
Assignment
5 - 24
No. 1
Value
display
ALM: Integrated alarm (The Integrated
out1 to
Alarm Assignment parameter must be
out2
set separately.)
ALM: Integrated alarm (The Integrated
sub1 to
Alarm Assignment parameter must be
sub4
set separately.)
Set the sum of the following values for
the alarms and errors to include in the
OR output. 0 to 255
Alarm 1: +1
Alarm 2: +2
Alarm 3: +4
alma
Alarm 4: +8
HB alarm: +16
HS alarm: +32
Input error: +64
RSP input error: +128
(Default: 49 (i.e., an OR of alarm 1, the
HB alarm, and the HS alarm))
No. 2
display
Advanced
alm
Function Setting
Level
Advanced
alm
Function Setting
Level
Advanced
0 to 255
Function Setting
Level
E5@C Digital Temperature Controllers User's Manual (H174)