Omron E5CC User Manual page 66

Digital
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

3 Part Names and Basic Procedures
Operation indicators
Keys
Key
Level Key
O
Mode Key
M
Down Key and Up
Key
D
U
Shift Key (PF Key)
S
3 - 6
Name
Remote SP
This indicator is lit while the SP Mode parameter is set to Remote
SP Mode.
This indicator flashes when there is an RSP input error in Remote
SP Mode.
Setting change
This indicator is lit while setting change protection is ON.
protection
Name
Overview
Selects the setting
level.
The next setting
level depends on
how long the key is
pressed.
Changes the
parameter that is
displayed within a
setting level.
Set the value.
Operates as a
user-defined
function key.
Description
Description
• In Operation Level
• Press once for less than 1 second to go to
Adjustment Level.
• Press for at least 3 seconds to go to Initial Setting
Level.
• In Adjustment Level
• Press once for less than 1 second to go to
Operation Level.
• Press for at least 3 seconds to go to Initial Setting
Level.
• In Initial Setting Level
• Press for at least 1 second to go to Operation
Level.
• Display amov (Move to Advanced Function
Setting Level) and then enter −169 to go to
Advanced Function Setting Level.
• Press once to go to the next parameter.
• Hold to go to the previous parameter.
• Hold the key to increment or decrement the value
quickly.
• Any changes in settings are applied at the following
times:
• After 3 seconds elapse
• When the M Key is pressed
• When the level is changed with the O Key
• Press the S to select the digit to change.
You can change the PF Setting parameter to assign
any of the following functions.
• Press the S Key for at least 1 second and then
specify one of the following functions:
RUN/STOP, auto/manual, autotuning, or canceling an
alarm latch
The PF Key operates as a Digit Shift Key by default.
Example: If you set the PF Setting parameter to STOP,
operation will stop when you press the PF Key for at
least 1 second.
• Press the PF Key once to display the Monitor/Setting
Item Level.
The parameter that is displayed is set in the
Monitor/Setting Item parameters in the Advanced
Function Setting Level.
E5@C Digital Temperature Controllers User's Manual (H174)