6 Parameters
sp-0
sp-1
sp-2
sp-3
sp-4
sp-5
sp-6
sp-7
These parameters set the set points when the multi-SP function is used.
The values set in these parameters can be selected by operating the keys on the front panel
or by using event inputs.
• When the set point has been changed, the set value of the set point (0 to 7) selected by
Function
the multi-SP inputs is also changed to the same value.
• The decimal point position depends on the selected sensor. During analog input, it
depends on the Decimal Point parameter setting.
Setting
Related Parameters
See
See
Process Value/Set Point (Operation Level): Page 6-8
Input Type (Initial Setting Level): Page 6-42
Event Input Assignment (Initial Setting Level): Page 6-55
Number of Multi-SP Points (Advanced Function Setting Level): Page 6-61
6 - 26
SP 0
SP 1
SP 2
SP 3
SP 4
SP 5
SP 6
SP 7
Setting range
SP lower limit to SP upper limit
The Number of Multi-SP Points parameter must be
set to 2 to 8 and the Event Input 1 Assignment to
Event Input 6 Assignment parameters must not be
set to "Multi-SP No. switching bit 0" to "Multi-SP
No. switching bit 2."
Unit
EU
E5@C Digital Temperature Controllers User's Manual (H174)
Default
0