Parameter Structure

• To execute user calibration, enter the password "1201" at the Move to Calibration Level parameter in
the Advanced Function Setting Level. The mode will be changed to the calibration mode, and adj will
be displayed.
• The Move to Calibration Level parameter may not be displayed when the user is doing the calibration
for the first time. If this happens, set the Initial Setting/Communications Protect parameter in the
Protect Level to 0 before moving to the Advanced Function Setting Level.
• The calibration mode is ended by turning the power OFF.
• The parameter calibrations in the calibration mode are structured as shown below.
Advanced Function
Setting Level
adj
30
Resistance
thermometer
M
0: Pt100
1: Pt100
2: Pt100
3: JPt100
4: JPt100
p390
p280
e20c
M
p 10
p 10
4543
M
str
no
M
Transfer output
*This function is displayed only for a Controller that has a transfer output.
calibration
When calibration has been performed after purchase, the user calibration information shown in the
following illustration will be displayed when moving to the Calibration Level.
E5@C Digital Temperature Controllers User's Manual (H174)
Display moves automatically according to input type.
Thermocouple or infrared
temperature sensor
5: K
7: J
11: E
12: L
15: N
19: W
20: PLII
t 54
t 24
e26b
b9a5
e220
M
M
M
t -6
t -6
4543
2988
0200
M
M
M
bia5
bia5
35b8
35b8
M
M
.adj
Current
Voltage input
input
25: 4 to 20 mA
27: 1 to 5 V
29: 0 to 10 V
26: 0 to 20 mA
28: 0 to 5 V
a 20
1V 5
2V10
c8e7
c7c3
b104
M
M
M
a
1
1V 1
2V 1
4677
5ac0
4ad9
M
M
M
30
A dot is displayed.
7 User Calibration
6: K
8: J
9,10: T
13,14: U
16: R
17: S
18: B
21: K140F/60C
22: K240F/120C
23: K280F/140C
24: K440F/220C
7 - 3